Rating and Use of UL489 Molded Case Circuit Breakers in APC Rack Power Distribution Products
Issue Rating and Use of UL489 Molded Case Circuit Breakers in APC Rack Power Distribution Products
Power Consumption of APC Rack Power Distribution Unit (PDU) / Automatic Transfer Switch (ATS) Products
Rack Power Distribution Unit (PDU) Type Total Power Consumption (no outlets "ON")
How accurate is the current monitor on my APC Rack Power Distribution Unit (PDU) and Rack Automatic Transfer Switch ?
Issue How accurate is the current monitor on my APC Rack Power Distribution Unit (PDU) and Rack Automatic Transfer Switch (ATS) ?
Can I plug my APC Rack-Mount Power Distribution Unit (Rack PDU) into a feed receptacle located in the under floor plenum? (Also applicable to Configurable & Modular Power Distribution)
Rack Power Distribution 1) per 645.4(3) the equipment is UL Listed 2) per 645.5(B)(1) the flexible cord and attachment plug cap do not exceed 15 ft. 3) per 645.5(D)(2) branch-circuit supply conductors to receptacles are properly installed in accordance with 300.11 4) 645.5(D) (5) specifically relates to "cables" used under the raised floor, and not "flexible cord" as is the IT equipment power cord.
AP8XXX Series Rack PDU Power Output Specifications (CAN & USB ports)
Product Line Rack Power Distribution (PDU) Models
AP8966 Rack PDU shows incorrect bank to phase relationships
... 4.0/rpdu2g v6.4.0, the AP8966 Rack Power Distribution Unit (PDU) shows incorrect bank to ...
50a 208v 3 Phase Rack PDU Load Ratings and Calculations Explained
Product Line 3 Phase Rack Power Distribution models