How does the predictive failure notification work on the fans in the ACSC cooling unit?

Issue:
How does the predictive failure notification work on the fans? 
 
Product line:
ACSC100, ACSC101
 
Environment:
InRow Cooling
 
Cause:
 
Resolution:
It compares the fans actual RPM to the command RPM. If the fans are +/- 800 RPM different from the expected, the alarm is given.