Resolution:
The SC should be powered from a dedicated circuit; the unit has very high in-rush current (>55 amps) that may overload the UPS every time the compressor turns on. If you must power the SC from a UPS, then it needs to be properly sized; a dedicated UPS would be preferred. Contact your Config team rep or Systems Engineer for additional assistance.