Information for Noise level of UPS Galaxy PW

 
 
Issue:
Information for Noise level of UPS Galaxy PW.
 
 
Product line:
Galaxy PW US
 

Environment:
Galaxy PW 150KVA US
Galaxy PW 225KVA US
 

Cause:
Customer needs UPS room noise level with Galaxy PW.
 

Resolution:
We publish this information. for Galaxy PW UPS.
 
Noise levels
Noise levels are measured according to standard ISO 3746 (NFS 31 027).
UPS noise levels are indicated below:
 
 
UPS rating in KVA 100 130 150 180 200 225
Noise level on normal floor (dBA) 62 63 64 65 67 68
 
The noise level is identical for linear and non-linear loads.
 
 
 
 
 
 
 