Issue:
What filter is being used for your InRow 300mm?
Product line:
InRow 300mm Units
Environment:
Data Center Cooling
Cause:
Resolution:
The filtration of conditioned air is extremely vital to maintaining the clean, particle-free environment required by electrical equipment. The system uses a <20% efficiency ASHRAE 52.1, 12.7 mm (1/2 in) washable, deep loading, large dust-holding filter that meets HF-1 standards for electronics (MERV 1 per ASHRAE 52.2).
Model | # of Filters Required |
ACSC10x | 1 |
ACRC10x | 2 |
ACRD10x | 2 |
ACRD20x | 2 |
ACRA10x | 2 |
x = various voltage range