Technical FAQs

Ask a Question

How to clear Humidifier Run Hours on a Chilled Water Uniflair Unit

Issue:
How to clear Humidifier Run Hours Violation.
 
Product line:
Uniflair: TDCV700X, TDCV1000X, TDCV1200X, TDCV1700X, TDCV2500X, TDCV3400X, TDCV4000X, TDCV4300X, TUCV700X, TUCV1000X, TUCV1200X, TUCV1700X, TUCV2500X, TUCV3400X, TUCV4000X, TUCV4300X, HDCV4500X, HDCV5000X
 
Environment:
All Serial Numbers
 
Cause:
Install, Repair
 
Resolution
 
Press PRG
 
Use the DOWN arrow to scroll to Hourmeter Settings
 
Press ENTER
 
Use the DOWN arrow to scroll to Humidifier Run Hours
 
Press ENTER twice.
 
Press the DOWN arrow once
 
Press ENTER again to clear run hours.
 
Press ESC three times to exit back to main menu
 
Was this helpful?
What can we do to improve the information ?